Cable Test Set - KPG 80kV

The devices series KPG 50-120kV have been designed as Cable Test Sets for DC voltage testing of Medium Voltage Power Cables.

There are 4 different versions (50kV/80kV/110kV/120kV) available. The devices are characterized by low weight and high output power. Thanks to the compact 2-part design, the units are easily portable and perfect to be used on site. The separate design of Operation- and High Voltage unit, a key switch, switch-on interlock and a protective ground circuit ensure maximum safety.

Field of application

  • Testing of newly installed cables an cable joints before commissioning
  • Testing at re-commissioning of cable systems or High Voltage systems after maintenance and repair
  • Regular preventive cable testing
  • Testing of electrical equipment
Technical data KPG 80kV
Power supply Mains operation, selectable 115/230 V ; 50/60 Hz
Output voltage
infinitely adjustable
0 ... 80 kV DC
negative polarity
Rated output current at max. output voltage 5 mA
Overcurrent trip > 7 mA
Voltage measuring range 0 ... 80 kV
Current measuring ranges 100 µA / 1 mA / 10 mA
Power consumption max. 900 VA
Included Ground- and Discharge Rod 80 kV / D.Energy 11250 J (4 µF at 75 kV) / 4-part design
Operating temperature
Storage temperature
-25 °C ... +55 °C
-40 °C ... +70 °C
Weight
   Operation unit
   High Voltage unit

13 kg
17 kg
Dimensions (W x H x D)
   Operation unit
   High Voltage unit

37 x 20 x 28 cm
21 x 36 x 31 cm

Characteristics

  • Easy operation
  • Robust construction, low weight
  • Compact, easily portable by modular design
  • Quick test setup on site
  • Overcurrent trip
  • Overvoltage protection
  • Voltage measurement direct at HV output
  • Protective ground circuit

Options

  • Transport case with trolley-function
  • Customized HV cables (shielded or unshielded)
  • Timer 1 … 60 minutes

Scope of supply

  • Operation unit with protective bag and cable storage
  • HV unit with HV outlet part
  • HV-connecting cable, length 2m
  • Connecting cable, HV unit to Operating unit, length 3m
  • Ground cable for station ground, length 3m
  • Ground cable for protective ground, length 3m
  • Mains lead
  • Ground- and Discharge rod 80kV, demountable, with ground cable and bag
  • Service pack
  • User manual